Free tool
Roof simulator
Build up your roof layer by layer. The simulator works out its U-value, checks the grant threshold and spots condensation risks, using the methods of the European standards.
Start from an example
Winter conditions for condensation 20 °C, 50 % / -5 °C, 80 %
Build-up, layer by layer
From the room to the outside: pick each material and its thickness, then set the order with the arrows.
Heated room
-
Softwood (boarding, sarking boards) 20 mm
-
Vapour barrier sd 18.00 m
-
PIR polyurethane (Utherm Sarking K) 140 mm
-
Breathable roofing underlay (HPV) sd 0.10 m
Ventilated air gap, then the roof covering
U-value of the roof 0.147W/m²·KRoof section
The temperature through the roof, and the dew point of the water vapour passing through it: as long as the dew point stays below the temperature, the vapour does not condense.
- Temperature
- Dew point
- Condensation
Layer details
| No. | Layer | Thickness (mm) | λ (W/m·K) | R (m²·K/W) | sd (m) | Temperature on the outer side (°C) |
|---|---|---|---|---|---|---|
| Surface exchange, inner side | 0.10 | 19.6 | ||||
| 1 | Softwood (boarding, sarking boards) | 20 | 0.130 | 0.15 | 1.00 | 19.1 |
| 2 | Vapour barrier | 18.00 | 19.1 | |||
| 3 | PIR polyurethane (Utherm Sarking K) | 140 | 0.022 | 6.45 | 8.40 | -4.6 |
| 4 | Breathable roofing underlay (HPV) | 0.10 | -4.6 | |||
| Surface exchange, outer side | 0.10 | -5.0 | ||||
| Total | 160 | 6.80 | 27.50 |
How it is worked out
- U-value following EN ISO 6946: surface resistances Rsi 0.10 and Rse 0.04 m²·K/W (heat rising towards the roof). Under a ventilated roof covering, anything beyond the air gap does not count and Rse is 0.10.
- Rafters or joists within a layer: combined method of the standard (average of the upper and lower limits), softwood with λ 0.13 W/m·K.
- Condensation: Glaser method (EN ISO 13788), between the rafters, in a steady winter state. It shows where vapour may condense; it does not work out drying over the year.
- Sarking boards: resistance declared by the manufacturer for each thickness made, as in the simulator on the Services page.
- Not counted: thermal bridges, fixings, workmanship defects, unventilated air gaps, summer comfort.
Where the values come from
- French Th-Bât rules, Materials booklet (housing ministry, 2017), the French version of the values of the European standard EN ISO 10456: plaster, timber, OSB, plywood, μ factor of mineral wool and polyurethane.
- Unilin datasheets (Utherm Sarking K and Utherm Sarking L Comfort) and STEICO (STEICOtherm dry, ACERMI certificate 13/134/897): thicknesses made, declared resistances, μ factor of the wood fibre.
- ACERMI certificates: Isover GR 32 (02/018/100, λ 0.032) and Rockwool Rockmur kraft (02/015/025, λ 0.035).
- French roofing and insulation codes (NF DTU 40.29, 45.10 and 31.2): vapour barrier Sd ≥ 18 m; breathable underlay (HPV) Sd ≤ 0.10 m (class Sd1). Change the sd value to match the datasheet of the product fitted.
- Grant thresholds: French energy-savings sheet BAR-EN-101 (R ≥ 6 for pitched roofs, R ≥ 7 for cold lofts), along with the other grant conditions (RGE contractor, household income).
Indicative results: they replace neither a thermal study nor a roofer’s on-site advice. The exact build-up of your roof is set during the free visit.